AQUALINE IRON, MANGANESE FILTERS
Aqualine Iron and Manganese filters thanks to special minerals; It can reduce the amount of iron and manganese in water up to 5ppm to drinking and utility water standards (Fe = 0.2 ppm - Mn = 0.05ppm). There is no need for any extra regent material for these special minerals. It also removes hydrogen sulfide, methane, free carbon dioxide and high concentrations of organic residues in water.
AQUALINE ARSENIC FILTERS
Arsenic element is one of the most abundant elements in nature, with properties between metal and nonmetal. It is a substance with carcinogenic and toxic properties. The most common types of inorganic arsenic in water are arsenite (As(III)) and arsenate (As(V)). The type and distribution of arsenic is determined by the pH of the water, its redox potential and the presence of complex ions such as sulfur, iron and calcium. Many people are at risk of arsenic poisoning due to naturally occurring groundwater arsenic pollution in many regions of the world. For this reason, Aqualine Arsenic Filter Systems solutions that we produce are used to reduce arsenic levels from 50µg/L, which was the previous value allowed by the World Health Organization (WHO), to below 10µg/L, and they are applied extremely successfully.
Since human health is prioritized in Aqualine filtration systems, the minerals used in our systems comply with world food norms.
Epoxy painted carbon steel tank
Maximum working pressure 6 bar
Time controlled backwash
Butterfly valves with pneumatic actuators (Optional Electric Actuator option)
F-1215 and F-1615 bottom collection structure octopus diffuser
Between F-2015 and F-2815, lower collection structure, mushroom diffuser on the mirror
PVC-U material surface piping (Optional galvanized surface piping option)
Sample taps and manometers at system entrances and exits
PLC based Siemens logo control panel (Optional touch screen option)
Electricity 220V /50 Hz / 1 pH
The supply of dry instrument air required for the operation of pneumatic valves is the responsibility of the customer. Recommended compressor capacity is minimum 100 Lt/min @ 8 bar.
Our company can produce Metal Tanks for Purification Systems that comply with Pressure Equipment Standards and are certified.
AD 2000 MERKBLATT
ASME SEC.VIII
EN 13445 (TÜV NORD SYSTEMS NOTIFIED BODY NUMBER NUMBER 0045 approved)